- The capacitor is fused at the electrode level
- Longer life at PSOC(Note1)cycle
- Excellent charge acceptance
- Suppression of sulfation which is the weakness of the lead-acid battery
- Improved charge-discharge rate. (1.5 times higher than our existing products)
- Reduced evenly charging frequency once a month. (Less than our recommended conditions)
- Unit structure and multiple superimposed loading is available
(Note1) PSOC: Partial Stage of Charge
- Renewable energy sector
- Wind power/Solar power generation
- Peak shift, load leveling
- Electric power regeneration application
- Repetitive large current charge and discharge application
- Others
- UB-1000: Approximately 4500 cycles (25℃, DOD70%, 0.23C_{10}A)
- UB-50-12: Approximately 4000 cycles (25℃, DOD70%, 1.0C_{10}A)
This is an expected value based on our recommended use condition, and different from a guaranteed value.
Type | Nominal voltage (V) |
10 hrs. rate Capacity (Ah) |
Nominal energy capacity (Wh) |
External dimensions (Approx. mm) | Weight (Approx. kg) |
Maximum current | Operating temperature range (℃) | |||
---|---|---|---|---|---|---|---|---|---|---|
Height | Width | Length | Charge | Discharge | ||||||
UB-1000 | 2 | 1000 | 2000 | 508 | 172 | 303 | 73 | 0.4C_{10}A | 0.6C_{10}A | 0~40 |
UB-50-12 | 12 | 50 | 600 | 220 | 363 | 128 | 22 | 0.5C_{10}A | 1.0C_{10}A | 0~40 |